Agricultural Equipment and Supplies 2023

239 Frost Protection Drinkers Heated 24 V drinking bowls – how do they work? Heating drinking water using drinking bowls is so easy! You only need at least one heated drinking bowl, a thermostat and a transformer (as 24 V operation). Which transformer for how many bowls? Simple! If you only want to use one drinking bowl with 80 W of power, a 100 VA transformer will suffice. If you also want to connect a 24 V heating cable, simply add the power consumption (= wattage) of the cable and this gives you the minimum power required for the transformer. Do not measure the transformer’s power too precisely, so you will have a buffer for extensions. Connection diagram 1. Mains connection 230 V, separately fused 2. Water connection, spur line or circulation system possible 3. Frost-protection thermostat 230 V (222794) 4. Junction box, protection class at least IP54 5. Transformer 230 V AC => 24 V AC, 100 W (222796), 200 W (222797), 300 W (222626), 400 W (222798) 6. Junction box, protection class at least IP54 7. 24 V supply cable for further heated drinking bowls or heating cables 8. 24 V supply cable for connecting to the drinking bowl 9. 24 V frost-protection heating line (22358, 223581) (if not connected to a circulating heat system) 10. Protective plate for the bite area (221975) 11. Pipe insulation 12. Heated drinking bowl (e.g. 222010) 230 V 24 V Bite area 24 V When choosing a transformer, ensure that you factor in the power loss caused by the supply cables. You will find a sample calculation and a table containing power loss values in this catalogue.